Zonescan Case Study 2 – Wessex Water, Trowbridge.

Vous êtes ici: Products > Acoustic Logging > Zonescan Case Study 2 – Wessex Water, Trowbridge.

Zonescan - screenshot
Zonescan - screenshot
A trial Zonescan survey carried for Wessex Water in Trowbridge produced a table of results as indicated below. This was carried out in the afternoon after a previous full survey of the DMA indicated this as an area of interest.
The area was a council estate just outside the town centre. The pipe material was cast iron, but no correlation had been carried out previously as there is no pipe fitting at the
end of the cul-de-sac. Surface sounding had highlighted a possible a leak location indicated by the red arrow on the map above.
Logged Results:      
Zonescan - screenshot Zonescan - screenshot Zonescan - screenshot Zonescan - screenshot
Logger 100093 Logger 100085 Logger 100090 Logger 100076
Loggers: 100090,100093, and, 100085 all indicate a classic leak noise profile. Logger 100076 indicates a very loud noise but also a wide profile. This logger is the logger closest to the leak but is located on the plastic meter blank in an MSM box located outside the second to last house in the cul-de-sac. The plastic fitting is dampening the sound and causing the wide profile.

Zonescan - screenshotDespite this potential problem fitting, logger 100076 recorded a noise signal for correlation that, when cross correlated with the noise signal recorded by logger 100093, produced the result on the right.

Surface sounding confirmed the location of the leak coincided exactly with the middle spike of the “fork” shaped correlation result.

The digital Zonescan logger recorded a noise of sufficient quality to correlate through a plastic fitting.

 

 

find.more.leaks